HYDROSTATION
Hydrostation is the new IE5 efficiency class electronic system for constant pressure…
In-line centrifugal pump with cast iron hydraulics, robust and available in single or twin versions and with 2 or 4 pole motors. Used in handling of liquids in circulation, heating and air conditioning systems in civil and industrial environments. Read more
Flow rate | from 3 to 220 m³/h |
Total head | from 10.7 m to 67.5 m |
Max. working pressure | 6 bar for LPC 32-100/40-100 10 bar for the rest of the range |
Max. temperature of the liquid | 10°C ÷ +50°C for LPC 32-100 -10°C ÷ +110°C for the rest of the range |
MEI | > 0.4 |
Poles | 2 and 4 |
Insulation class | F |
Protection degree | IP55 |
Voltage | Three-phase 3~230/400V ±10% up to 4 kW Three-phase 3~400V/690V ±10% from 7.5 kW and above |
Pump body | Cast iron |
Impeller | Cast iron |
Shaft | Stainless steel AISI 420 (EN 1.4021) |
Mechanical seal | Carbon/Silicon Carbide/EPDM |
Motor support | Cast iron |
What is the correct position and installation for circulators and in-line pumps?
Please check the pictograms in the instruction manual.
Can I change the circulator’s settings?
If the circulator has a display, its functions can be changed according to the system’s requirements.
How do I check the in-line pump's direction of rotation?
The in-line pump’s direction of rotation has to be checked every time a new installation is carried out.
We suggest to follow the steps given below:
The correct direction of rotation is clockwise.
If it’s not, reverse the phases of the pump’s motor.
What wattage can be used for star connections?
Above 7.5 kW, we suggest to use this kind of start-up in order to limit very high inrush currents.
What is the circulator's supply voltage?
The circulator’s supply voltage is 230V
What percentage of glycol can be used in the system when the circulator is used for cooling?
The maximum amount of glycol that can be used is 20%.
Contact us